                              | Reasons and Solutions for magnetic  flowmeter showing negative value |  4-01-2020 The failure of the electromagnetic flow  meter during operation is often caused by factors such as the adhesion layer on  the liner of the flow sensor ,lightning electric shock and environmental conditions.if  the electromagnetic flowmeters have a negative flow value during use, there are  likely to be several reasons: 
                              Electromagnetic flow meter  sensor is not installed according to the flow direction indicator, causing the  flow to be reversely measured .at this time ,the instantaneous flow rate is a  negative value.Solution: reinstall the electromagnetic flowmeters and follow  the sensor flow direction.Signal line of the flow sensor  is reversed .the electromagnetic flow meter has the function of the forward and  reverse measurement, so the reverse flow will be displayed. Solution: the sensor signal line can be switched correctly.The pipe is empty or the liquid  is not filled, and there are air and bubbles. At this time ,the phenomenon that  the negative number or the flow value is suddenly large or small is displayed. Solution: the shrinkage or tilting installation can be used  to fill the pipe with the measured medium, which allows the flowmeters to have  measurement condition. There is also a case where the flow rate of the  electromagnetic flowmeter is negative .when the valve is opened, the instantaneous  flow will case the pipe liquid to recirculate ,resulting in a negative value.
   
   